Details

Fire protection housing free standing housing F30-dc3500

ES31:12244-L-Detect
Art-Nr.: 33026

Fire protection housing F30 as empty free standing housing for the integration of fire control panel dc3500

  • Suitable for ensuring functionality of safety systems in case of fire for more than 30 minutes.
  • The fire protection housing can be used in necessary evacuation and emergency paths. The functionality of the integrated fire control panel is monitored by a smoke detector.
  • Incombustible execution with surface coating A2 –s1, d0
  • Standard surface HPL with chemical and humidity resistance
  • Circumferential fire safety seal foaming in case of fire
  • Empty housing with high mechanical and chemical stability
  • Functionality ensurance by high waste heat and thermal load insulation, cold-smokeproof in combination with EBEL:VENTO, EBEL:NETZ and smoke detector PL 3300 O with base
  • Integrated air aeration system via backplate prepared for ventilator mounting for EBEN:VENTO and power supply EBEL:NETZ as accessories
  • Monitoring of the integrated fire control panel dc3500 for smoke contamination by smoke detector and thermal disconnection of the ventilator EBEL:VENTO
  • On Wall Housing with door stop left suitable for dc3500
  • Opening angle of door approx. 180°
  • 2-point-door locking with swivel lever and closing by two-bit key
  • Cable entry 2 x on top and 2 x at buttom with cable sealing for bundle or single cable entry
  • Including 2 x fastening lugs for wall mounting from outside
  • Including premounted fasteing system for the mounting of the FCP dc3500 and optional power supply BF 362-5, consisting of two C-rails with variable spacers ( from 40-160 mm) and 5 equaliser bars
  • Necessary fastening elements (sliding nut, fittings) included in delivery
  • Removable door and lower edge protection for integration and mounting
  • Supportable base with removable front cover for easy transportation
  • 288 PE space units; 12 HE Height units; 2 BE width units
  • Fire protection housing and fire control panel tested by MPA Dresden, complying to the conditions of MLAR-2005
  • The fire protection housing can be used in necessary evacuation and emergency paths. The functionality of the integrated fire control panel is monitored by a smoke detector. Detector and base are not included in the delievery and have to be ordered sperately.
  • The integrated aeration system in combination with external ventilator EBEL: VENTO ensures optimum ventilation of the inbuilt electronic modules and the necessary airflow for the inbuilt fixed batteries. The ventilator EBEL:VENTO is included in the scope of delivery.
  • For the voltage supply of the ventilator EBEL: VENTO the power supply EBEL:NETZ should be used. This power supply is not included in the scope of delivery and has to be ordered seperately (article 33027).
  • An optional mounting and connection of the pressure cell EBEL:VENT-AU 33028 for the air monitoring allows an additional and permanent functionality monitoring of the aeration system in regard of availability. The analysation of all messagesDie Auswertung aller can be done with a fire event control matrix and can be documented.
Protection class IP 42, Protection class II
Dimensions (H x W x D) Inner: 1800 mm x 500 mm x 440 mm, <br>Outer: 2068 mm x 668 mm x 604 mm
Weight 354 kg
Colour Housing lightgrey (similar RAL 7035)
Standards Fire resistance class F30 according DIN 4102-2
Further Approvals DIBt Z-86.1-46, Z-86.1-47
Remarks The pressure cell is not included in the delivery and has to be ordered seperately
Title Type Size  
PIB_DE_33026_BSG-F30.pdf Product information sheet 132 KB Download

Information Service

If you would like to participate in one of our company's services, be informed individually by e-mail or by post, the processing of personal data is necessary. In this context, all companies are required by law to obtain the consent of the person concerned

We would be pleased to inform you free of charge about:

  • the latest fire alarm technology products
  • Trade fairs and events
  • Training dates
  • as well as news from Detectomat Systems GmbH

To Registration