- Exact pollution recognition by an additional independent measuring chamber
- Detector sensitivities automatically calibrated and programmable
- Fault monitoring of the measurement chamber signal and Loop 3000-electronics
- Periodic sensor test
- Automatic and manual addressing with Loop 3000
- Integrated Isolator and T-branch option
- Alarm output to control parallel indicator
- Functions completely integrated via Loop 3000-protocol
- Presence and absence switching with freely selectable sensitivities
- Storage of last maintenance date
- Multicolour LED for alarm (red) and fault (yellow)
- Multicolour LED for alarm (red) and fault (yellow)
Products fire alarm systems
Optical smoke detector with isolator, Design 05-silver
Optical smoke detector for Loop 3000 with 2 optical sensors for earliest fire detection and indication and with bidirectional isolator according to EN 54-7 and EN 54-17
documents
-
Additional information and downloads on our products and services are available in the protected website area. A one-time registration is necessary to receive the
A one-time registration is necessary to receive the personal login data .
Product Information
Technical Specifications
| Supply Voltage | 15 V to 32 V DC on to 2-wire bus (max. 34 V DC) |
| Quiescent Current | 280 µA |
| Alarm Current | 5 mA |
| Output | OC: max. 10 mA for parallel indicator or buzzer |
| Ambient Temperature | -10°C to +60°C |
| Humidity | max. 95% |
| Protection Class | IP 40 |
| Material | ABS, ESG-Glass |
| Standards | DIN EN 54-7, EN 54-17 |
| Color variant | Silver |
| Dimensions (H x D) | appr. 48 mm x 112 mm (wit |
| Response Sensitivity | Adjustable in 5 sensitivity levels |
| DIN EN | 54-7, 54-17 |
| VdS-Approval | G 204089 |