- According to the requirements of VdS 2496 and VdS 2540
- Monitoring of the status via Loop 3000
- Automatic and manual addressing with Loop 3000
- Integrated bi-directional isolator
- Modular housing for the easy mounting onto a DIN rail into dc3500
Products fire alarm systems
Extinguishing control module, installation kit
Intelligent Extinguishing control module for loop3000 system with bi-directional isolator to control One-Zone-Extinguishing panels. With two supervised inputs and one potential free optical-relay-output. The status of the module is displayed in the dc 3500 fire control panel.
documents
-
Additional information and downloads on our products and services are available in the protected website area. A one-time registration is necessary to receive the
A one-time registration is necessary to receive the personal login data .
Product Information
Technical Specifications
| Supply Voltage | 17 V to 32 V DC, 2-wire-Bus |
| Quiescent Current | appr. 460 µA |
| Alarm Current | 6 mA |
| Output | 1 optical relay potential free |
| Operating Temperature | -20°C to +60°C |
| Storage Temperature | -25°C to +85°C |
| Protection Class | IP 30 - installed in fire control panel dc3500 |
| Dimensions (H x W x D) | 72 mm x 83 mm x 33 mm |
| Weight | 30 g |
| Standards | EN 54-17: 2005; EN 54-18:2005 |
| Remarks | pro dc3500 only 1 ECM-module usable. Its not allowed to use it in a stitch. |