- 6 potential free relay outputs 30 V/2 A (Alarm, Fault and four free ones)
- 2 potential free individually programmable inputs
- 1 external control line 24 V/800 mA supervised for accoustic signal devices
- 1 OC-input to integrate the door contact
- Evaluation of emergency paths alram and fault
- System-plug to connect to dc 3500 system
- System-socket to connect additional modules to the dc3500 system
Products fire alarm systems

Basic module for dc 3500, protected
Basic module as component for the dc3500 with special coating against condensing water.
documents
-
Additional information and downloads on our products and services are available in the protected website area. A one-time registration is necessary to receive the
A one-time registration is necessary to receive the personal login data .
Product Information
Technical Specifications
Supply Voltage | 24 V DC ( +10 %), 5 V DC ( ±10 %), 3,3 V DC ( ±10 %) |
Quiescent Current | 40 mA (3,3 V), 5mA (5V), 31mA (24 V) |
Alarm Current | 43 mA (3,3 V), 5 mA (5V), 75 mA (24 V) |
Ambient Temperature | -5°C to +40°C |
Humidity | 5% to 95% (not condensing) |
Dimensions (H x W x D) | 125 mm x 100 mm x 20 mm |
Weight | 78 g |