Products fire alarm systems

Product Image

Optical smoke detector with isolator

This product is replacing part no 30011 and is 100 % compatible!

Optical smoke detector for Loop 3000 for earliest fire detection and indication and with bidirectional isolator according to EN 54-7 and EN 54-17. The detector has in intelligent pollution compensation.

Art-Nr.: 33974 | PL 3300 O, Version 2025

documents

  • Additional information and downloads on our products and services are available in the protected website area. A one-time registration is necessary to receive the

    A one-time registration is necessary to receive the personal login data .

Product Information

  • Special algorithm for intelligent pollution detection of the smoke measurement chamber
  • Detector sensitivities automatically adapted and programmable
  • Fault monitoring of the measurement chamber signal and Loop 3000 electronics
  • Periodic sensor test
  • Automatic and manual addressing on Loop 3000
  • Integrated isolator and T-branch option
  • Alarm output to control parallel indicator
  • Functions completely integrated via Loop 3000 protocol
  • Presence and absence switching with selectable sensitivities
  • Storage commissioning date and last maintenance date
  • Multicolour LED for alarm (red) and fault (yellow)
  • Delivery including protective cover for installation phase
  • Compatibel to CONUS II Sounder and CONUS II SF (with battery)

Technical Specifications

Supply Voltage 15 V to 32 V DC on 2-wire bus (max. 34 V DC)
Quiescent Current 280 µA
Alarm Current 5 mA
Output OC: max. 15 mA for parallel indicator or buzzer
Ambient Temperature -10°C to +60°C
Humidity max. 95 %
Protection Class IP 40
Dimensions (H x W x D) appr. 44 mm x 97 mm (with base)
Weight appr. 80 g
Material ABS
Color Housing white (similar to RAL 9003)
Standards EN 54-7, EN 54-17
Remarks Replacing 30011
Response Sensitivity Adjustable in 5 sensitivity levels
VdS-Approval G 202002

Certificates / Approvals

  • Additional information and downloads on our products and services are available in the protected website area. A one-time registration is necessary to receive the

    A one-time registration is necessary to receive the personal login data .