Products fire alarm systems

Product Image

Thermal detector with isolator

This product is replacing part no 30010 and is 100 % compatible!

Thermal detector with fixed and rate of rise temperature settings for Loop 3000 for earliest fire detection and indication in all environments with difficult ambient conditions and with bidirectional isolator, according to EN 54-5 and EN 54-17.

Art-Nr.: 33982 | PL 3300 T, Version 2025

documents

  • Additional information and downloads on our products and services are available in the protected website area. A one-time registration is necessary to receive the

    A one-time registration is necessary to receive the personal login data .

Product Information

  • Thermal detector, certified according to EN 54-5 in the temperature classes A1R, A1S (A1) and A2R, A2S (A2) and EN 54-17
  • Individual use of the thermal measurement according EN 54-5 in the sensitivity levels 2 to 5 as maximum detector (static --> A1S, A2S) or as rate-of-rise detector with maximum threshold (differential and static --> A1R, A2R)
  • Individual change of detector class for sensitivity levels 2 to 5 using Easy Check 3000
  • Periodic sensor test
  • Automatic and manual addressing with Loop 3000
  • Integrated Isolator and T-branch option
  • Alarm output to control parallel indicator
  • Functions completely integrated via Loop 3000 protocol
  • Presence and absence switching with selectable sensitivities
  • Storage of last maintenance date
  • Multicolour LED for alarm (red) and fault (yellow)
  • Delivery including protective cover for installation phase
  • Compatibel to CONUS II Sounder and CONUS II SF (with battery)

Technical Specifications

Supply Voltage 15 V to 32 V DC on 2-wire bus (max. 34 V DC)
Quiescent Current 280 µA
Alarm Current 5 mA
Output OC: max. 15 mA for parallel indicator or buzzer
Ambient Temperature -10°C to +60°C
Humidity max. 95 %
Protection Class IP 40
Dimensions (H x W x D) appr. 52 mm x 97 mm (with base)
Weight appr. 80 g
Material ABS
Color Housing white (similar to RAL 9003)
Standards EN 54-5, EN 54-17
Remarks Replacing 30010
Response Sensitivity EN 54-5: A1S, A1R, A2S, A2R
VdS-Approval G 203037