- input for an external power supply
- configurable input for the secondary line (conventional detectors and manual call points line)
- One output to connect a remote action indicator located less than 3 meters away
Products fire alarm systems
TCM 1 zone module for DC510
Intelligent Input module for the connection of one conventional detector zone to D-Loop with bidirectional isolator according to EN 54-18
Art-Nr.: DL-510-TCM-SB | MBALC
documents
No documents.
Product Information
Technical Specifications
| Supply Voltage | 30 V to 41 V DC on 2-wire bus (nom. 40 V DC) |
| Quiescent Current | 200 µA |
| Alarm Current | 1 mA |
| Output | max 30 mA at 24 V DC |
| Ambient Temperature | -30°C to +70°C |
| Storage Temperature | +10°C to +50°C |
| Humidity | max. 93 % |
| Protection Class | IP 43 |
| Dimensions (H x W x D) | 185 x 130 x 70 mm |
| Weight | 350 g |
| Material | PP |
| Color | Grey |
| Inputs | disconnection at 146 mA / 62 mA as ATEX paramreter |
Certificates / Approvals
-
Additional information and downloads on our products and services are available in the protected website area. A one-time registration is necessary to receive the
A one-time registration is necessary to receive the personal login data .